HEPA Filters

HEPA Filters
APPLICATIONS
These HEPA filters are designed to meet exact specifications in high efficiency commercial or industrial applications. These filters are used where a high degree of cleanliness is required and contaminants must be removed to protect health, products and building interiors. These filters are ideal in a variety of applications including: hospitals, manufacturing plants, microelectronic component assembly, negative air machines, biological hoods and food processing environments.

GLASS MICROFIBER MEDIA
Gently pleated glass microfiber media is separated with rolled edged aluminum separators to offer open air flow and to stabilize the media pack.


STANDARD FEATURES AND OPTIONS
Frames are available in either 3/4 inch high density particleboard and 18 gauge galvanized metal (26 gauge galvanized metal for the 95% HEPA). An external neoprene gasket is standard and is located on the downstream side. A rubber based two-part fire-retarding sealer bonds the media and separators to the interior of the frame. Headers are available as an option on metal frame filters. Optional expanded metal face guards are also available. High capacity and turbine style filters are available. These filters are rated to withstand temperatures at a continuous 180 degrees Fahrenheit. Higher temperature models are available. Each filter is packed in a heavy-duty carton to help protect the filter from damage during transit. Rated Class 2 under U.L. Standard 900.

SPECIFICATIONS:
The filter element shall be factory constructed by pleating a continuous sheet of glass microfiber media into uniform spaced pleats which are separated by rolled edge corrugated aluminum. The efficiency shall be 95%, 99.97% or 99.99% based on a near-monodispersed .30 micron size particle. This filter pack shall be encased in a rigid frame of 3/4” particleboard or 18 gauge galvanized steel for the 99.97% and 99.99% efficiencies (26 gauge galvanized metal frame is used for the 95% filters). The frame shall not exceed 5-7/8" or 11-1/2" in depth, and standard tolerances shall be +/- 1/16" on height and width. A closed cell neoprene gasket shall be applied to the filter. Each filter shall be packaged into a heavy-duty carton. Filters shall be listed U.L. Class 2 under Std. 900.

HEPA Air Conditioning Filters and Filtration System for Metal Frame and Wood Housing, if your looking for high efficiency Filters for commercial and industrial Air Conditioning Filtration System for Metal Frame and Wood Housing our HEPA Filters may be the solution for you.

CLICK HERE TO SEE: Optional Configurations for HEPA Filters including Headers